Power factor correction calculator

Work out the capacitive kvar that raises a lagging power factor to a target, and how much the line current falls.

Electrical power and current Updated Free, no sign-up

Load
kW

Lagging, from the meter

Target

Common targets

Lagging; check your tariff

Supply
Supply
V

Capacitive reactive power to add

42.13kvar

From power factor 0.8 to 0.95 on 100 kW.

Line current, each line
180.4 → 151.9 A
Current reduction
15.79%
Apparent power
125 → 105.3 kVA
Reactive power, lagging
75 → 32.87 kvar
Next size up in 5 kvar steps
45 kvar
Power factor with 45 kvar
0.9578

Choose the bank and its detuning with a harmonic and resonance check.

How it’s calculated
  1. tan φ = tan(cos⁻¹ PF)=0.75 now, 0.3287 at target
  2. Qc = P × (tan φ1 − tan φ2)=100 × (0.75 − 0.3287)=42.13 kvar
  3. I = P × 1000 ÷ (√3 × VLL × PF)=100 × 1000 ÷ (1.732 × 400 × 0.95)=151.9 A

Raising 100 kW from a power factor of 0.8 to 0.95 needs 42.13 kvar of capacitance, and cuts the line current by 15.79%.

Tip: Size correction from measured kW and power factor over a representative period, not from a single reading or the transformer rating.

How to calculate the kvar for power factor correction

Power factor correction adds capacitive kvar to cancel part of the lagging kvar that motors and transformers draw. The capacitance needed is the real power times the difference between the tangents of the two phase angles. Raising a 300 kW load from a power factor of 0.8 to 0.95 takes 126.4 kvar and cuts the line current by about 16%.

Capacitive kvar to add

Qc = P × (tan φ1 − tan φ2)

P is the real power in kW, φ1 the phase angle now and φ2 the angle at the target, each found as cos−1 of the power factor. The real power does not change; only the reactive part does.

Using the multiplier table

Qc = P × k

k = tan φ1 − tan φ2 depends only on the two power factors, so it can be read from a table. From 0.8 to 0.95, k = 0.421: every kW needs 0.421 kvar.

Current after correction

I2 = I1 × PF1 ÷ PF2

For the same real power, current falls in proportion to the rise in power factor. That frees capacity in cables and transformers and reduces their losses.

Correcting to exactly 1.0 is rarely worth it. The last few hundredths need a lot of kvar, and a bank sized for full load can push the power factor leading when the load is light. Most sites aim for 0.95 to 0.98, or whatever the tariff sets.

Power factor correction examples

A 300 kW load from 0.8 to 0.95

tan(cos−1 0.8) = 0.75 and tan(cos−1 0.95) = 0.329, so the bank needs 300 × (0.75 − 0.329) = 126.4 kvar. At 400 V the line current falls from 541.3 A to 455.8 A.

Capacitive reactive power to add 126.4 kvar Open in the calculator

A 200 kW plant at 480 V

From 0.82 to 0.95 the plant needs 73.86 kvar. A 75 kvar bank, the next size up in 25 kvar steps, brings the power factor to 0.9516.

Capacitive reactive power to add 73.86 kvar Open in the calculator

A large step to 0.98

From 0.75 to 0.98 a 150 kW load needs 101.8 kvar, and the line current falls by 23.47%. The first half of the kvar does most of the work: the move from 0.95 to 0.98 alone accounts for about 19 kvar.

Capacitive reactive power to add 101.8 kvar Open in the calculator

Power factor correction multiplier table (kvar per kW)

Multiply the real power in kW by the figure for your present and target power factors to get the kvar to add.

Power factor correction multiplier table (kvar per kW), values in kvar/kW
Power factor nowTo 0.90 (kvar/kW)To 0.95 (kvar/kW)To 0.98 (kvar/kW)To 1.00 (kvar/kW)
0.600.8491.0051.1301.333
0.650.6850.8400.9661.169
0.700.5360.6920.8171.020
0.720.4800.6350.7610.964
0.740.4250.5800.7060.909
0.760.3710.5260.6520.855
0.780.3180.4740.5990.802
0.800.2660.4210.5470.750
0.820.2140.3690.4950.698
0.840.1620.3170.4430.646
0.860.1090.2650.3900.593
0.880.0550.2110.3370.540

Download this table (CSV)

Questions about power factor correction

How do I calculate the capacitor size for power factor correction?

Multiply the real power in kW by tan φ1 − tan φ2, or by the multiplier in the table above. The answer is the capacitive kvar at the supply voltage.

What power factor should I correct to?

The level your tariff rewards, commonly 0.95 or above. Going to 1.0 costs more kvar for little gain and risks a leading power factor at light load.

Can I use the power factor my meter shows?

Only if harmonics are low. A meter’s total power factor includes distortion, which capacitors cannot correct and which can cause resonance with them. Where total harmonic distortion is significant, use displacement power factor and a detuned bank.

Will power factor correction reduce my energy bill?

It reduces reactive energy and kVA demand charges where the tariff has them, and slightly reduces losses in cables and transformers. It does not reduce the kWh the load itself uses.

Limits of this result

  • Do not apply this displacement-power triangle to total power factor where harmonic distortion is material.
  • Harmonic spectrum, resonance, detuning, capacitor voltage/current stress, switching transients, step size, duty cycle and utility limits require an engineering study.
  • The entered voltage is used only to compare ideal line current before and after correction; it does not size a capacitor or protective device.
  • This mode assumes an initially lagging load and a higher lagging target; leading-power-factor correction is outside scope.

Measure it continuously

Size correction from a representative period, not one reading. A ZEM records power factor and demand continuously, before and after the bank goes in.

Related guides

Sources

  1. Power factor correction and harmonic filtering in electrical plants (opens in a new tab) (PDF) ABB, Technical Application Paper 1SDC007107G0201, July 2008
  2. Electrical devices: electrotechnical formulas (opens in a new tab) (PDF) ABB, 1SDC010001D0202