Industrial protocols

Wired M-Bus primary-address schedule checker

Check a wired M-Bus primary-address schedule for duplicates, unconfigured devices and reserved or special addresses.

Calculate

Planned devices
devices
Plans above 250 devices cannot use one unique ordinary primary address per device; segmentation and secondary-selection design remain separate.
Enter one address per device, separated by commas, spaces or new lines.

Worked example

Primary-address status

Valid primary plan 

Unique assigned addresses 1–250
addresses
Remaining primary-address capacity
244 addresses
Entries still at address 0
devices
Duplicate primary addresses
None
Reserved or special values entered
None

The entered count matches and every device has a unique ordinary primary address. Bus and meter commissioning checks still apply.

Method and assumptions

Formula

Valid assigned primary addresses = 1…250; remaining capacity = 250 − unique assigned addresses

Address 0 is unconfigured. Values 251–255 have reserved, secondary-selection or broadcast roles and are not ordinary unique device addresses.

Limits of this result

  • This checks an address schedule; it does not discover, select or re-address a meter.
  • Secondary-address uniqueness and wildcard selection must be verified with the exact meter and master implementation.
  • Bus power, capacitance, topology and timing are separate commissioning checks.

Technical sources

  1. OMS Specification Volume 2 — Primary CommunicationOMS Group · Issue 5.0.1, 2023-12
  2. M-Bus data-link layer documentationM-Bus Usergroup · documentation revision 4.8