0-10 V signal scaling calculator

Convert an analogue voltage signal to the value it represents, or a value to the voltage a sensor should output, for 0-10 V, 2-10 V, 1-5 V or any linear range.

Sensors and signals Updated Free, no sign-up

You enter, in numbered orderCalculated

Signal lowSignalValue
Signal highSignalValue
Unit

Signal, Vsignal range

0246810
020406080100

Value, %

Signal voltage
Measured value
Position in the span50

Inside the signal range

Type the ends of the range or the signal, or drag the cursor along the scale.

Measured value

50%

Position in the span
50%
How it’s calculated
  1. Value = low + (V − Vlow) × (high − low) ÷ (Vhigh − Vlow)=0 + (5 − 0) × (100 − 0) ÷ (10 − 0)=50 %

Choose the input that reads this signal.

Build a system

5 V on a 0-10 V signal ranged 0 to 100% reads 50%.

Tip: A 2-10 V signal reserves voltages below 2 V for faults rather than valid readings. An open wire does not necessarily read 0 V: fault detection depends on the receiver input bias or diagnostics, and an unconnected input may float.

Example values
What do you want to calculate?
Convert
Signal range

Common signals

V
V

Shown with the result, such as %RH or °C

Signal
V

How to convert 0-10 V to engineering units

A 0-10 V sensor outputs a voltage in proportion to its reading: 0 V at the bottom of its range, 10 V at the top. To convert, find how far the voltage is along the signal span and apply that share to the measuring range. 5 V on a 0 to 100% humidity sensor is 50%. The same method works for 2-10 V, 0-5 V and 1-5 V signals.

Voltage to value

value = low + (V − Vlow) × (high − low) ÷ (Vhigh − Vlow)

Vlow and Vhigh are the signal limits (0 and 10 V, or 2 and 10 V), and low and high are the readings at those limits.

Value to voltage

V = Vlow + (value − low) × (Vhigh − Vlow) ÷ (high − low)

Use this to check a sensor: at a known condition, work out the voltage it should give and measure it.

0-10 V to percentage

% = V × 10

For a plain 0-10 V signal each volt is 10% of span. For 2-10 V, the span is 8 V: % = (V − 2) ÷ 8 × 100.

With a 2-10 V or 1-5 V live-zero signal, 0 V is outside the valid measuring range. A low voltage can indicate a broken wire only when the receiver input has defined bias or diagnostics: an open input may float instead of reading 0 V. A plain 0-10 V signal cannot identify a broken wire from a zero reading alone.

0-10 V scaling examples

A 2-10 V humidity sensor at 6.4 V

The span is 8 V, and 6.4 V is 4.4 V above the 2 V live zero: 4.4 ÷ 8 = 55% of span, so the reading is 55 %RH.

Measured value 55 %RH Open in the calculator

A 0-10 V temperature sensor ranged −20 to 80 °C

Each volt is 10 °C of the 100 °C range. At 3.7 V the reading is −20 + 3.7 × 10 = 17 °C.

Measured value 17 °C Open in the calculator

Checking a 1-5 V pressure transmitter

At 4 bar on a 0 to 16 bar range the transmitter is at a quarter of span, so it should output 1 + 0.25 × 4 = 2 V. A 1-5 V signal is often a 4-20 mA loop measured across a 250 Ω resistor.

Signal voltage 2 V Open in the calculator

0-10 V and 2-10 V to percentage table

Each whole volt as a share of span for the two most common building-automation signals.

Signal (V)0-10 V2-10 V
00%Below range
110%Below range
220%0%
330%12.5%
440%25%
550%37.5%
660%50%
770%62.5%
880%75%
990%87.5%
10100%100%

Download this table (CSV)

Questions about 0-10 V scaling

How do I convert 0-10 V to a percentage?

Multiply the voltage by 10: 7.5 V is 75%. For 2-10 V, subtract 2, divide by 8 and multiply by 100: 7.5 V is 68.75%.

Should I use 0-10 V or 4-20 mA?

Voltage signals are simple and common in HVAC, but cable resistance and electrical noise shift them, so keep runs short. A 4-20 mA loop is unaffected by cable resistance within its supply budget and suits long runs; see the 4-20 mA scaling calculator.

Can I read a 4-20 mA signal as a voltage?

Yes, across a precision resistor: 250 Ω turns 4-20 mA into 1-5 V. Check that the loop supply has enough voltage left to drive the resistor.

Limits of this result

  • The calculation does not include source impedance, input loading, ground offset, isolation or cable noise.
  • A nonlinear sensor requires its own transfer function or calibration table.

Log the signal continuously

ZIO and ZVO read 4-20 mA and 0-10 V instruments and send the readings to the Gateway over the wireless mesh.

Related guides

Sources

  1. NI-DAQmx raw-data voltage scaling (opens in a new tab) National Instruments, updated 2023-04-20
  2. Introduction to FOUNDATION Fieldbus Scaling (opens in a new tab) National Instruments, updated 2025