Socomec · ModbusDIRIS A-40

Read-only starter map for the DIRIS A-40 using Socomec communication table v1.7.4. It covers instantaneous voltage, current, power, power factor and frequency plus total import/export energy. It does not claim compatibility with the DIRIS A-41.

Register map

Zero-based Modbus PDU addresses. Everything the points share is stated once below; the table carries what differs between them.

Function
FC3 read holding registers
Endianness
big endian
Offset
0
Word order
normal
Byte order
normal
Reporting
every 60 s
Access
read only, export off

Points 32

Swipe to see every column

Download
PointPDU addressFormatMultiplierUnit
Frequency 18442 uint32×0.001 Hz
Voltage L1-N 18444 uint32×0.01 V
Voltage L2-N 18446 uint32×0.01 V
Voltage L3-N 18448 uint32×0.01 V
Voltage L1-L2 18452 uint32×0.01 V
Voltage L2-L3 18454 uint32×0.01 V
Voltage L3-L1 18456 uint32×0.01 V
Current L1 18458 uint32×0.001 A
Current L2 18460 uint32×0.001 A
Current L3 18462 uint32×0.001 A
Neutral Current 18464 uint32×0.001 A
Total Active Power 18476 int32×1 W
Total Reactive Power 18478 int32×1 var
Total Apparent Power 18484 uint32×1 VA
Total Power Factor 18486 int16×0.001 -
Active Power L1 18488 int32×1 W
Active Power L2 18490 int32×1 W
Active Power L3 18492 int32×1 W
Reactive Power L1 18494 int32×1 var
Reactive Power L2 18496 int32×1 var
Reactive Power L3 18498 int32×1 var
Apparent Power L1 18512 uint32×1 VA
Apparent Power L2 18514 uint32×1 VA
Apparent Power L3 18516 uint32×1 VA
Power Factor L1 18518 int16×0.001 -
Power Factor L2 18519 int16×0.001 -
Power Factor L3 18520 int16×0.001 -
Import Active Energy 19843 uint32×1 kWh
Export Active Energy 19846 uint32×1 kWh
Import Reactive Energy 19849 uint32×1 kvarh
Export Reactive Energy 19852 uint32×1 kvarh
Total Apparent Energy 19855 uint32×1 kVAh

What the download changes

When applied in Edge, the file replaces the selected device's current Modbus sensor list with these 32 read-only points. It does not change the Gateway connection, server address, Modbus unit ID, device enable state or export identifiers. Back up or duplicate a customised definition before applying it.

Import, apply, then prove one known value

  1. 1
    Download the reviewed JSON

    Sign in with an account that has approved Edge download access.

  2. 2
    Import in Edge

    Open Settings → Device Templates, choose Import, and select the downloaded file.

  3. 3
    Apply to the exact model

    Use a new or backed-up device definition, then choose its existing Gateway connection and unit address. Applying the template replaces that definition's current sensor list.

  4. 4
    Commission before rollout

    Check identity, value, unit and timestamp against one known condition before enabling exports or repeating the setup.

Sources

  1. MODBUS tables of DIRIS A-40 (opens in a new tab) Socomec · A-40 v1.7.4 · January 2022
  2. How to read measurement data via Modbus on Socomec's Digiware metering system (opens in a new tab) (PDF) Socomec · Technical note · 02 March 2026

This template applies only to Socomec DIRIS A-40. Product names and trademarks belong to their respective owners; publication does not imply endorsement or a commercial relationship.