Siemens · Modbus7KM2112-0BA00-3AA0 (firmware 2.4.2)

Read-only starter map for SENTRON PAC3200 ordering code 7KM2112-0BA00-3AA0 at firmware 2.4.2. It covers instantaneous voltage, current, power, power factor, frequency and voltage/current THD from Siemens' measured-variable table, and excludes the four-register Double energy counters that Edge does not currently decode.

Register map

Zero-based Modbus PDU addresses. Everything the points share is stated once below; the table carries what differs between them.

Function
FC3 read holding registers
Endianness
big endian
Format
float32
Multiplier
×1
Offset
0
Word order
normal
Byte order
normal
Reporting
every 60 s
Access
read only, export off

Points 32

Swipe to see every column

Download
PointPDU addressUnit
Voltage L1-N 1 V
Voltage L2-N 3 V
Voltage L3-N 5 V
Voltage L1-L2 7 V
Voltage L2-L3 9 V
Voltage L3-L1 11 V
Current L1 13 A
Current L2 15 A
Current L3 17 A
Apparent Power L1 19 VA
Apparent Power L2 21 VA
Apparent Power L3 23 VA
Active Power L1 25 W
Active Power L2 27 W
Active Power L3 29 W
Reactive Power L1 31 var
Reactive Power L2 33 var
Reactive Power L3 35 var
Power Factor L1 37 -
Power Factor L2 39 -
Power Factor L3 41 -
Voltage THD L1 43 %
Voltage THD L2 45 %
Voltage THD L3 47 %
Current THD L1 49 %
Current THD L2 51 %
Current THD L3 53 %
Frequency 55 Hz
Total Apparent Power 63 VA
Total Active Power 65 W
Total Reactive Power 67 var
Total Power Factor 69 -

What the download changes

When applied in Edge, the file replaces the selected device's current Modbus sensor list with these 32 read-only points. It does not change the Gateway connection, server address, Modbus unit ID, device enable state or export identifiers. Back up or duplicate a customised definition before applying it.

Import, apply, then prove one known value

  1. 1
    Download the reviewed JSON

    Sign in with an account that has approved Edge download access.

  2. 2
    Import in Edge

    Open Settings → Device Templates, choose Import, and select the downloaded file.

  3. 3
    Apply to the exact model

    Use a new or backed-up device definition, then choose its existing Gateway connection and unit address. Applying the template replaces that definition's current sensor list.

  4. 4
    Commission before rollout

    Check identity, value, unit and timestamp against one known condition before enabling exports or repeating the setup.

Sources

  1. SENTRON PAC3200 Manual (opens in a new tab) (PDF) Siemens · 02/2008 · A5E01168664B-04
  2. Data Exchange between S7-1200 and SENTRON PAC via MODBUS TCP (Set 22) (opens in a new tab) (PDF) Siemens · V14.0 · 06/2017 · firmware 2.4.2

This template applies only to Siemens 7KM2112-0BA00-3AA0 (firmware 2.4.2). Product names and trademarks belong to their respective owners; publication does not imply endorsement or a commercial relationship.