Siemens · Modbus7KM2112-0BA00-3AA0 (firmware 2.4.2)
Read-only starter map for SENTRON PAC3200 ordering code 7KM2112-0BA00-3AA0 at firmware 2.4.2. It covers instantaneous voltage, current, power, power factor, frequency and voltage/current THD from Siemens' measured-variable table, and excludes the four-register Double energy counters that Edge does not currently decode.
Register map
Zero-based Modbus PDU addresses. Everything the points share is stated once below; the table carries what differs between them.
- Function
- FC3 read holding registers
- Endianness
- big endian
- Format
- float32
- Multiplier
- ×1
- Offset
- 0
- Word order
- normal
- Byte order
- normal
- Reporting
- every 60 s
- Access
- read only, export off
Points 32
| Point | PDU address | Unit |
|---|---|---|
| Voltage L1-N | 1 | V |
| Voltage L2-N | 3 | V |
| Voltage L3-N | 5 | V |
| Voltage L1-L2 | 7 | V |
| Voltage L2-L3 | 9 | V |
| Voltage L3-L1 | 11 | V |
| Current L1 | 13 | A |
| Current L2 | 15 | A |
| Current L3 | 17 | A |
| Apparent Power L1 | 19 | VA |
| Apparent Power L2 | 21 | VA |
| Apparent Power L3 | 23 | VA |
| Active Power L1 | 25 | W |
| Active Power L2 | 27 | W |
| Active Power L3 | 29 | W |
| Reactive Power L1 | 31 | var |
| Reactive Power L2 | 33 | var |
| Reactive Power L3 | 35 | var |
| Power Factor L1 | 37 | - |
| Power Factor L2 | 39 | - |
| Power Factor L3 | 41 | - |
| Voltage THD L1 | 43 | % |
| Voltage THD L2 | 45 | % |
| Voltage THD L3 | 47 | % |
| Current THD L1 | 49 | % |
| Current THD L2 | 51 | % |
| Current THD L3 | 53 | % |
| Frequency | 55 | Hz |
| Total Apparent Power | 63 | VA |
| Total Active Power | 65 | W |
| Total Reactive Power | 67 | var |
| Total Power Factor | 69 | - |
What the download changes
When applied in Edge, the file replaces the selected device's current Modbus sensor list with these 32 read-only points. It does not change the Gateway connection, server address, Modbus unit ID, device enable state or export identifiers. Back up or duplicate a customised definition before applying it.
Import, apply, then prove one known value
- 1Download the reviewed JSON
Sign in with an account that has approved Edge download access.
- 2Import in Edge
Open Settings → Device Templates, choose Import, and select the downloaded file.
- 3Apply to the exact model
Use a new or backed-up device definition, then choose its existing Gateway connection and unit address. Applying the template replaces that definition's current sensor list.
- 4Commission before rollout
Check identity, value, unit and timestamp against one known condition before enabling exports or repeating the setup.
Sources
- SENTRON PAC3200 Manual (opens in a new tab) (PDF)
- Data Exchange between S7-1200 and SENTRON PAC via MODBUS TCP (Set 22) (opens in a new tab) (PDF)
This template applies only to Siemens 7KM2112-0BA00-3AA0 (firmware 2.4.2). Product names and trademarks belong to their respective owners; publication does not imply endorsement or a commercial relationship.