Schneider Electric · ModbusSchneider iEM3350

Read-only starter map for the Schneider Electric iEM3350 Modbus RTU meter. It contains the 23 Float32 measurements Schneider documents for this model: current, voltage, active power, power factor, frequency and active import energy.

Register map

Zero-based Modbus PDU addresses. Everything the points share is stated once below; the table carries what differs between them.

Function
FC3 read holding registers
Endianness
big endian
Format
float32
Multiplier
×1
Offset
0
Word order
normal
Byte order
normal
Reporting
every 60 s
Access
read only, export off

Points 23

Swipe to see every column

Download
PointPDU addressUnit
Current L1 2999 A
Current L2 3001 A
Current L3 3003 A
Average Current 3009 A
Voltage L1-L2 3019 V
Voltage L2-L3 3021 V
Voltage L3-L1 3023 V
Average Voltage L-L 3025 V
Voltage L1-N 3027 V
Voltage L2-N 3029 V
Voltage L3-N 3031 V
Average Voltage L-N 3035 V
Active Power L1 3053 kW
Active Power L2 3055 kW
Active Power L3 3057 kW
Total Active Power 3059 kW
Total Power Factor 3083 -
Frequency 3109 Hz
Total Active Energy Import 45099 kWh
Partial Active Energy Import 45107 kWh
Active Energy Import L1 45111 kWh
Active Energy Import L2 45113 kWh
Active Energy Import L3 45115 kWh

What the download changes

When applied in Edge, the file replaces the selected device's current Modbus sensor list with these 23 read-only points. It does not change the Gateway connection, server address, Modbus unit ID, device enable state or export identifiers. Back up or duplicate a customised definition before applying it.

Import, apply, then prove one known value

  1. 1
    Download the reviewed JSON

    Sign in with an account that has approved Edge download access.

  2. 2
    Import in Edge

    Open Settings → Device Templates, choose Import, and select the downloaded file.

  3. 3
    Apply to the exact model

    Use a new or backed-up device definition, then choose its existing Gateway connection and unit address. Applying the template replaces that definition's current sensor list.

  4. 4
    Commission before rollout

    Check identity, value, unit and timestamp against one known condition before enabling exports or repeating the setup.

Sources

  1. Energy meters iEM3100 / iEM3200 / iEM3300 series user manual (opens in a new tab) Schneider Electric · DOCA0005EN-16 · 2026
  2. Current, voltage, power, power factor and frequency register table (opens in a new tab) Schneider Electric · DOCA0005EN-16
  3. Energy, energy by tariff and input metering register table (opens in a new tab) Schneider Electric · DOCA0005EN-16
  4. Pinned mbmd iEM3000 RS-485 implementation (opens in a new tab) volkszaehler.org contributors · eef6045ae30e46b9ddaf175f0dfbb4c4e26247e3

This template applies only to Schneider Electric iEM3350. Product names and trademarks belong to their respective owners; publication does not imply endorsement or a commercial relationship.