Janitza · ModbusUMG 103 (firmware 0.931+)

Read-only starter map for the Janitza UMG 103 running firmware 0.931 or later. Uses FC04, Janitza's documented Big-Endian address form and 32-bit IEEE-754 values.

Register map

Zero-based Modbus PDU addresses. Everything the points share is stated once below; the table carries what differs between them.

Function
FC4 read input registers
Endianness
big endian
Format
float32
Multiplier
×1
Offset
0
Word order
normal
Byte order
normal
Reporting
every 60 s
Access
read only, export off

Points 32

Swipe to see every column

Download
PointPDU addressUnit
Voltage L1-N 19000 V
Voltage L2-N 19002 V
Voltage L3-N 19004 V
Voltage L1-L2 19006 V
Voltage L2-L3 19008 V
Voltage L3-L1 19010 V
Apparent Current L1 19012 A
Apparent Current L2 19014 A
Apparent Current L3 19016 A
Neutral Current (vector sum) 19018 A
Active Power L1 19020 W
Active Power L2 19022 W
Active Power L3 19024 W
Total Active Power 19026 W
Apparent Power L1 19028 VA
Apparent Power L2 19030 VA
Apparent Power L3 19032 VA
Total Apparent Power 19034 VA
Reactive Power L1 19036 VAr
Reactive Power L2 19038 VAr
Reactive Power L3 19040 VAr
Total Reactive Power 19042 VAr
Fundamental Power Factor L1 19044 -
Fundamental Power Factor L2 19046 -
Fundamental Power Factor L3 19048 -
Frequency 19050 Hz
Active Energy Total L1-L3 19060 Wh
Delivered Active Energy Total L1-L3 19076 Wh
Apparent Energy Total L1-L3 19084 VAh
Reactive Energy Total L1-L3 19092 VArh
Inductive Reactive Energy Total L1-L3 19100 VArh
Capacitive Reactive Energy Total L1-L3 19108 VArh

What the download changes

When applied in Edge, the file replaces the selected device's current Modbus sensor list with these 32 read-only points. It does not change the Gateway connection, server address, Modbus unit ID, device enable state or export identifiers. Back up or duplicate a customised definition before applying it.

Import, apply, then prove one known value

  1. 1
    Download the reviewed JSON

    Sign in with an account that has approved Edge download access.

  2. 2
    Import in Edge

    Open Settings → Device Templates, choose Import, and select the downloaded file.

  3. 3
    Apply to the exact model

    Use a new or backed-up device definition, then choose its existing Gateway connection and unit address. Applying the template replaces that definition's current sensor list.

  4. 4
    Commission before rollout

    Check identity, value, unit and timestamp against one known condition before enabling exports or repeating the setup.