Carlo Gavazzi · ModbusEM24-DIN PFA/PFB/X RS-485
Read-only starter map for the EM24-DIN PFA, PFB and X RS-485 models covered by Carlo Gavazzi's Communication Protocol Version 4 Revision 0. Uses FC04, the documented physical offsets and scaled signed integers.
Register map
Zero-based Modbus PDU addresses, with the decode, scale and reporting the download applies.
| Edge point | PDU address | Function | Format | Decode | Scale | Reporting | Unit |
|---|---|---|---|---|---|---|---|
| Voltage L1-N | 0 | FC4 | int32 | Big endian · word swapped · normal byte order | ×0.1 · offset 0 | Every 60 s · export off · read only | V |
| Voltage L2-N | 2 | FC4 | int32 | Big endian · word swapped · normal byte order | ×0.1 · offset 0 | Every 60 s · export off · read only | V |
| Voltage L3-N | 4 | FC4 | int32 | Big endian · word swapped · normal byte order | ×0.1 · offset 0 | Every 60 s · export off · read only | V |
| Voltage L1-L2 | 6 | FC4 | int32 | Big endian · word swapped · normal byte order | ×0.1 · offset 0 | Every 60 s · export off · read only | V |
| Voltage L2-L3 | 8 | FC4 | int32 | Big endian · word swapped · normal byte order | ×0.1 · offset 0 | Every 60 s · export off · read only | V |
| Voltage L3-L1 | 10 | FC4 | int32 | Big endian · word swapped · normal byte order | ×0.1 · offset 0 | Every 60 s · export off · read only | V |
| Current L1 | 12 | FC4 | int32 | Big endian · word swapped · normal byte order | ×0.001 · offset 0 | Every 60 s · export off · read only | A |
| Current L2 | 14 | FC4 | int32 | Big endian · word swapped · normal byte order | ×0.001 · offset 0 | Every 60 s · export off · read only | A |
| Current L3 | 16 | FC4 | int32 | Big endian · word swapped · normal byte order | ×0.001 · offset 0 | Every 60 s · export off · read only | A |
| Active Power L1 | 18 | FC4 | int32 | Big endian · word swapped · normal byte order | ×0.1 · offset 0 | Every 60 s · export off · read only | W |
| Active Power L2 | 20 | FC4 | int32 | Big endian · word swapped · normal byte order | ×0.1 · offset 0 | Every 60 s · export off · read only | W |
| Active Power L3 | 22 | FC4 | int32 | Big endian · word swapped · normal byte order | ×0.1 · offset 0 | Every 60 s · export off · read only | W |
| Apparent Power L1 | 24 | FC4 | int32 | Big endian · word swapped · normal byte order | ×0.1 · offset 0 | Every 60 s · export off · read only | VA |
| Apparent Power L2 | 26 | FC4 | int32 | Big endian · word swapped · normal byte order | ×0.1 · offset 0 | Every 60 s · export off · read only | VA |
| Apparent Power L3 | 28 | FC4 | int32 | Big endian · word swapped · normal byte order | ×0.1 · offset 0 | Every 60 s · export off · read only | VA |
| Reactive Power L1 | 30 | FC4 | int32 | Big endian · word swapped · normal byte order | ×0.1 · offset 0 | Every 60 s · export off · read only | VAr |
| Reactive Power L2 | 32 | FC4 | int32 | Big endian · word swapped · normal byte order | ×0.1 · offset 0 | Every 60 s · export off · read only | VAr |
| Reactive Power L3 | 34 | FC4 | int32 | Big endian · word swapped · normal byte order | ×0.1 · offset 0 | Every 60 s · export off · read only | VAr |
| Average Voltage L-N | 36 | FC4 | int32 | Big endian · word swapped · normal byte order | ×0.1 · offset 0 | Every 60 s · export off · read only | V |
| Average Voltage L-L | 38 | FC4 | int32 | Big endian · word swapped · normal byte order | ×0.1 · offset 0 | Every 60 s · export off · read only | V |
| Total Active Power | 40 | FC4 | int32 | Big endian · word swapped · normal byte order | ×0.1 · offset 0 | Every 60 s · export off · read only | W |
| Total Apparent Power | 42 | FC4 | int32 | Big endian · word swapped · normal byte order | ×0.1 · offset 0 | Every 60 s · export off · read only | VA |
| Total Reactive Power | 44 | FC4 | int32 | Big endian · word swapped · normal byte order | ×0.1 · offset 0 | Every 60 s · export off · read only | VAr |
| Power Factor L1 | 50 | FC4 | int16 | Big endian · normal word order · normal byte order | ×0.001 · offset 0 | Every 60 s · export off · read only | – |
| Power Factor L2 | 51 | FC4 | int16 | Big endian · normal word order · normal byte order | ×0.001 · offset 0 | Every 60 s · export off · read only | – |
| Power Factor L3 | 52 | FC4 | int16 | Big endian · normal word order · normal byte order | ×0.001 · offset 0 | Every 60 s · export off · read only | – |
| Total Power Factor | 53 | FC4 | int16 | Big endian · normal word order · normal byte order | ×0.001 · offset 0 | Every 60 s · export off · read only | – |
| Frequency | 55 | FC4 | int16 | Big endian · normal word order · normal byte order | ×0.1 · offset 0 | Every 60 s · export off · read only | Hz |
| Import Active Energy | 62 | FC4 | int32 | Big endian · word swapped · normal byte order | ×0.1 · offset 0 | Every 60 s · export off · read only | kWh |
| Import Reactive Energy | 64 | FC4 | int32 | Big endian · word swapped · normal byte order | ×0.1 · offset 0 | Every 60 s · export off · read only | kVArh |
| Export Active Energy | 92 | FC4 | int32 | Big endian · word swapped · normal byte order | ×0.1 · offset 0 | Every 60 s · export off · read only | kWh |
| Export Reactive Energy | 94 | FC4 | int32 | Big endian · word swapped · normal byte order | ×0.1 · offset 0 | Every 60 s · export off · read only | kVArh |
What the download changes
When applied in Edge, the file replaces the selected device's current Modbus sensor list with these 32 read-only points. It does not change the Gateway connection, server address, Modbus unit ID, device enable state or export identifiers. Back up or duplicate a customised definition before applying it.
Import, apply, then prove one known value
- 1Download the reviewed JSON
Sign in with an account that has approved Edge download access.
- 2Import in Edge
Open Settings → Device Templates, choose Import, and select the downloaded file.
- 3Apply to the exact model
Use a new or backed-up device definition, then choose its existing Gateway connection and unit address. Applying the template replaces that definition's current sensor list.
- 4Commission before rollout
Check identity, value, unit and timestamp against one known condition before enabling exports or repeating the setup.
Ready to import
Revision 1.0.0, reviewed 20 Sept 2026.