ABB · ModbusM4M 20 / M4M 30 (map v1.3O)

Read-only starter map for the ABB M4M 20 and M4M 30 rows common to the official Modbus map v1.3O. It covers phase and line voltage, phase current, active/reactive/apparent power, frequency, power factor and phase voltage/current THD. Four-register energy counters are excluded because Edge does not currently decode 64-bit Modbus integers.

Register map

Zero-based Modbus PDU addresses. Everything the points share is stated once below; the table carries what differs between them.

Function
FC3 read holding registers
Endianness
big endian
Offset
0
Word order
normal
Byte order
normal
Reporting
every 60 s
Access
read only, export off

Points 32

Swipe to see every column

Download
PointPDU addressFormatMultiplierUnit
Voltage L1-N 23298 uint32×0.1 V
Voltage L2-N 23300 uint32×0.1 V
Voltage L3-N 23302 uint32×0.1 V
Voltage L1-L2 23304 uint32×0.1 V
Voltage L3-L2 23306 uint32×0.1 V
Voltage L1-L3 23308 uint32×0.1 V
Current L1 23312 uint32×0.01 A
Current L2 23314 uint32×0.01 A
Current L3 23316 uint32×0.01 A
Total Active Power 23322 int32×0.01 W
L1 Active Power 23324 int32×0.01 W
L2 Active Power 23326 int32×0.01 W
L3 Active Power 23328 int32×0.01 W
Total Reactive Power 23330 int32×0.01 var
L1 Reactive Power 23332 int32×0.01 var
L2 Reactive Power 23334 int32×0.01 var
L3 Reactive Power 23336 int32×0.01 var
Total Apparent Power 23338 int32×0.01 VA
L1 Apparent Power 23340 int32×0.01 VA
L2 Apparent Power 23342 int32×0.01 VA
L3 Apparent Power 23344 int32×0.01 VA
Frequency 23346 uint16×0.01 Hz
Total Power Factor 23360 int16×0.001
L1 Power Factor 23361 int16×0.001
L2 Power Factor 23362 int16×0.001
L3 Power Factor 23363 int16×0.001
Voltage THD L1 23808 uint16×0.1 %
Voltage THD L2 23936 uint16×0.1 %
Voltage THD L3 24064 uint16×0.1 %
Current THD L1 24576 uint16×0.1 %
Current THD L2 24704 uint16×0.1 %
Current THD L3 24832 uint16×0.1 %

What the download changes

When applied in Edge, the file replaces the selected device's current Modbus sensor list with these 32 read-only points. It does not change the Gateway connection, server address, Modbus unit ID, device enable state or export identifiers. Back up or duplicate a customised definition before applying it.

Import, apply, then prove one known value

  1. 1
    Download the reviewed JSON

    Sign in with an account that has approved Edge download access.

  2. 2
    Import in Edge

    Open Settings → Device Templates, choose Import, and select the downloaded file.

  3. 3
    Apply to the exact model

    Use a new or backed-up device definition, then choose its existing Gateway connection and unit address. Applying the template replaces that definition's current sensor list.

  4. 4
    Commission before rollout

    Check identity, value, unit and timestamp against one known condition before enabling exports or repeating the setup.

Sources

  1. M4M Modbus communication manual (opens in a new tab) ABB · 2CSG445050D0201 · v1.05 · 26 February 2021
  2. M4M Modbus map (opens in a new tab) ABB · 9AKK107492A7627 · v1.3O · 23 October 2023

This template applies only to ABB M4M 20 / M4M 30 (map v1.3O). Product names and trademarks belong to their respective owners; publication does not imply endorsement or a commercial relationship.