EPISENSOR | PULSE METER ACCEPTANCE RECORD Revision: 22 September 2026 Guide: https://episensor.com/knowledge-base/pulse-meter-commissioning-and-reconciliation One record for each pulse connection. Keep it with the site documents. Keep credentials, passwords and access tokens out of this file. 1. SOURCE METER Site and location: _______________________________________________________ Meter make, model and serial: ____________________________________________ Quantity measured (electricity, water, gas, heat): ________________________ Output type (dry contact / open collector / open drain / voltage): _________ Output terminals and polarity: ___________________________________________ Pulse weight, as read on the meter (with units): _________________________ Pulse width and minimum gap (from the manual): ____________________________ Photograph of nameplate and terminals taken? (yes / no): __________________ 2. COUNTER Counter model and serial: ________________________________________________ Input number and configuration: __________________________________________ Input limits (max rate, min on time, min off time): ________________________ Counter width in bits (counter and receiving system): _____________________ 3. RATE CHECK Maximum credible load or flow: ___________________________________________ Pulse rate at maximum (Hz): ______________________________________________ Inside the counter's limits? (yes / no): __________________________________ Time to rollover at maximum rate: ________________________________________ 4. KNOWN-COUNT TEST Pulses produced or observed: ____________________________________________ Raw count change: _______________________________________________________ Bounce or double counting seen? (yes / no): _______________________________ 5. RECOVERY TESTS Network interruption: count kept? (yes / no): _____________________________ Gateway restart: count kept? (yes / no): __________________________________ Counter power interruption (if safe and supported): ________________________ Duplicate counts after retransmission? (yes / no): _________________________ 6. RECONCILIATION Meter register Raw count Time Start: ______________ ____________ ________ End: ______________ ____________ ________ Change: ______________ ____________ Converted change (raw count x pulse weight): _____________________________ Difference and explanation: ______________________________________________ 7. ACCEPTANCE Accepted by: ____________________________ Date: _______________________ Open items and owners: ___________________________________________________ _________________________________________________________________________