EPISENSOR | MODBUS RS-485 ACCEPTANCE RECORD Revision: 22 September 2026 Guide: https://episensor.com/knowledge-base/modbus-rs485-commissioning One record for each RS-485 bus. Keep it with the site documents. Keep credentials, passwords and access tokens out of this file. 1. MASTER AND SERIAL SETTINGS Master or interface, model, serial and firmware: __________________________ Baud rate / data bits / parity / stop bits: _______________________________ Two-wire or four-wire: ___________________________________________________ 2. TOPOLOGY Trunk route and length (attach a sketch): _________________________________ Terminator positions (both ends only): ____________________________________ Bias source (one point only): ____________________________________________ Common conductor, shield and earthing: ____________________________________ Repeaters or isolators and their positions: _______________________________ 3. DEVICES (one line per device) Unit ID Make / model Firmware Register map revision _______ _____________________ _________ __________________________ _______ _____________________ _________ __________________________ _______ _____________________ _________ __________________________ 4. POINT MAP CHECKS (one line per data type or device) Unit ID Point FC Offset Type / order Raw words Decoded Display _______ ________ __ ______ ____________ ___________ _______ _______ _______ ________ __ ______ ____________ ___________ _______ _______ _______ ________ __ ______ ____________ ___________ _______ _______ 5. TIMING Polling cycle, calculated: _______________________________________________ Polling cycle, measured in normal operation: ______________________________ Slowest device response seen: ____________________________________________ Timeout and retry settings: ______________________________________________ 6. FAILURE TESTS One device disconnected: others still polled? (yes / no): __________________ Missing values marked stale? (yes / no): __________________________________ Master restart: counters and totals correct? (yes / no): ___________________ Write commands (if any): feedback and safe state tested? (yes / no / n/a): __ 7. ACCEPTANCE Accepted by: ____________________________ Date: _______________________ Open items and owners: ___________________________________________________ _________________________________________________________________________