EPISENSOR | ENERGY MONITORING ACCEPTANCE RECORD Revision: 18 October 2026 Guide: https://episensor.com/knowledge-base/energy-monitoring-commissioning-checklist One record for each site. Attach the point schedule and the interface records (pulse, M-Bus, Modbus, analogue) for the points that use them. Keep credentials, passwords and access tokens out of this file. 1. SITE AND VERSIONS Site and address: ________________________________________________________ Gateway model and serial: ________________________________________________ Edge version and configuration export reference: _________________________ Receiving platform and version (if any): _________________________________ Point schedule revision: _________________________________________________ Site test owner: _________________________________________________________ Equipment and receiving-platform owners: _________________________________ Agreed acceptance limits approved by / date: ______________________________ 2. POINT CHECKS (one line for each point, or attach a table) Point ID Circuit/asset Device/channel Unit Source value Displayed value Pass ________ _____________ ______________ ____ ____________ _______________ ____ ________ _____________ ______________ ____ ____________ _______________ ____ ________ _____________ ______________ ____ ____________ _______________ ____ Checked under a second operating state? (yes / no): _______________________ Phase pairing checked on three-phase meters? (yes / no): __________________ Sign convention (import positive / export positive): ______________________ For each point check, attach a test record with the fields below. Agree the limit before testing. Do not use a reading from the same meter register as an independent accuracy reference. Test ID and point ID: ____________________________________________________ Operating state and test time (include UTC offset): _______________________ Comparison (same source register / independent reference): ________________ Reference instrument or register, unit and resolution: ____________________ Expected result and agreed tolerance: _____________________________________ Observed source value / displayed or exported value: ______________________ Result (pass / fail / not done), with reason: _____________________________ Retained proof (file or record reference): ________________________________ Checked by: ______________________________________________________________ 3. TIME AND QUALITY Clock source for the Gateway: ____________________________________________ Timestamp meaning (source time / arrival time): ___________________________ Interval label (start / end of interval): _________________________________ A stale point shows as stale, not zero? (yes / no): _______________________ Agreed stale-data limit / observed delay: _________________________________ Agreed clock-offset limit / measured offset: ______________________________ 4. FAILURE TESTS Test Start time End time What the data showed One device off __________ _________ _______________________ Gateway restart __________ _________ _______________________ Upstream link down __________ _________ _______________________ Upstream link restored __________ _________ _______________________ For each failure test, retain the approved action, expected result, observed result and evidence reference. Mark a test not done if it is unsafe or out of scope; agree any alternative with the equipment and site owners. 5. DELIVERY TO THE RECEIVER Records expected for the outage window: ___________________________________ Records received: ________________________________________________________ Duplicates: ______________ Gaps: ______________ Late records kept? ______ Receiver query or export reference / time window: _________________________ Original timestamps preserved? (yes / no): _________________________________ 6. CONTROL (only if in scope) Approved test and owner: _________________________________________________ Command sent / accepted / feedback / measured result: ______________________ 7. HANDOVER Owner for stale data and alarms: _________________________________________ Owner for mapping changes: _______________________________________________ Owner for updates and backups: ___________________________________________ 8. ACCEPTANCE Tests not done, with reasons: ____________________________________________ Accepted by: ____________________________ Date: _______________________ Open items and owners: ___________________________________________________ _________________________________________________________________________ Keep failed results alongside their retests. An open item or a test not done is not a pass. Record who accepted an exception and the reason. Test ID / original result and evidence: ___________________________________ Correction / owner / due date: ____________________________________________ Retest time / result / evidence: __________________________________________ Exception accepted by / date / reason (if any): ___________________________ 9. REPEAT THE INSTALLATION AT ANOTHER SITE Use a blank record for each site. Reuse the test method and agreed template, never another site's results. Check the local point mapping, CT ratios, equipment versions and receiver destination before applying a configuration. Fleet or rollout reference: ______________________________________________ Shared point-schedule template revision: _________________________________ Shared test-method revision: _____________________________________________ Site-specific changes and approval reference: _____________________________ Keep one rollout register with these columns (or attach an existing register): Site ID | Configuration revision | Test owner | Evidence reference | Accepted by and date | Open items / owner / retest date Site ID: _________________________________________________________________ Configuration revision / differences from the template: ___________________ Test owner / evidence reference: __________________________________________ Accepted by and date: _____________________________________________________ Open items / owner / retest date: __________________________________________ Repeat for each site. Retain the site's source-to-receiver checks separately from fleet-level summaries, so a missing test cannot disappear in an average.